ADA Door Closer Compliance in Atlanta
ADA door closer compliance in Atlanta comes down to two numbers on interior doors: a 5 pound maximum opening force and a closing time of at least 5 seconds.
Direct line (470) 256-0441
- Atlanta only
- Call, no forms
- Cites the 2010 ADA Standards and NFPA 80

ADA door closer compliance in Atlanta: the short answer
ADA door closer compliance in Atlanta is measured against section 404 of the 2010 ADA Standards for Accessible Design on doors that are part of an accessible route. Two numbers matter for a closer: 5 pounds (22.2 N) maximum to push or pull an interior hinged door open (404.2.9) and at least 5 seconds for the door to move from 90 degrees open to 12 degrees from the latch (404.2.8.1).
ADA door closer compliance in Atlanta reads the 5 pound figure as, in the words of the Standards' advisory, the continuous force needed to fully open the door, not the force to overcome inertia, and it excludes retracting latch bolts. Fire doors take the minimum opening force the administrative authority allows. The spring sets the continuous force and the main speed valve sets the closing time, so a closer set too strong or too fast fails.
ADA door closer compliance in Atlanta is a measurement job, done with a force gauge and a stopwatch instead of by feel, and this page explains the numbers without certifying any door. Closer settings are covered under door closer adjustment, and fire doors under fire door closer repair.
ADA door closer compliance in Atlanta: quick facts and sources
Maximum force to open an interior hinged door: 2010 ADA Standards, section 404.2.9.
2010 ADA Standards, 404.2.9Minimum time for the closer to move the door from 90 to 12 degrees: 2010 ADA Standards, section 404.2.8.1.
2010 ADA Standards, 404.2.8.1Minimum closing time for spring hinges, from 70 degrees open to closed: 2010 ADA Standards, section 404.2.8.2.
2010 ADA Standards, 404.2.8.2Height range above the floor for operable parts of door hardware: 2010 ADA Standards, sections 404.2.7 and 309.4.
2010 ADA Standards, 404.2.7 and 309.4- Opening force, 404.2.9
- Interior hinged doors and sliding or folding doors are limited to 5 pounds (22.2 N) to open, and the limit does not apply to the force to retract latch bolts or disengage other devices that hold the door closed. 2010 ADA Standards, section 404
- Closing time, 404.2.8.1
- Door closers are adjusted so that from 90 degrees open the time to move to 12 degrees from the latch is 5 seconds minimum. 2010 ADA Standards, section 404
- Spring hinges, 404.2.8.2
- Spring hinges take 1.5 seconds minimum to close from 70 degrees open to closed. 2010 ADA Standards, section 404
- Operable hardware, 404.2.7
- Handles, pulls, latches and locks are operable with one hand, with no tight grasping, pinching or twisting of the wrist, 5 pounds maximum to activate (309.4), and sit 34 to 48 inches above the floor. 2010 ADA Standards, section 404
- Exterior doors
- Section 404.2.9 gives its 5 pound figure for interior hinged doors and for sliding and folding doors, and lists no figure for exterior hinged doors, so ask the building owner or the local code office. 2010 ADA Standards, section 404
- Reduced-force caution
- LCN cautions that a closer adjusted for ADA or other reduced opening force may not provide enough power to reliably close and latch a door. LCN concealed closer guide
How a ADA door closer compliance call in Atlanta works
Call and describe the door and the complaint
Say whether the door is hard to push or pull, or closes too fast, and whether it is interior, exterior or fire-rated.
Measure opening force and closing time
A force gauge measures opening force and a stopwatch measures the 90-degree-to-12-degree closing time.
Adjust or replace, then measure again
The sweep and spring power are set, an oversized closer is replaced, and the door is checked to still latch.
How much does ADA door closer compliance cost in Atlanta?
How much ADA door closer compliance work costs in Atlanta depends on how many doors are checked and what each closer needs, so this page gives no figures. The factors are:
- Number of doors tested. Each door is measured on its own.
- Adjust or replace. A closer that cannot meet both numbers is replaced with one sized for the door.
- Door type. Interior, exterior and fire-rated doors follow different rules.
- Measuring and re-measuring. Opening force and closing time are checked before and after the work.
- Door condition. Hinges, seals and building air pressure change the force a closer has to overcome.
For a figure on your door, call for a quote at (470) 256-0441.
Door too heavy or closing too fast? Call now.
Describe the door, and ADA door closer compliance work in Atlanta starts with measuring it.
What each number means in practice
The 5-pound opening force
The 5 pounds limit is, in the words of the Standards' advisory to 404.2.9, the continuous application of force necessary to fully open the door. It is not the initial force needed to overcome the inertia of the door, and it does not include the force to retract a latch bolt. The closer's spring is the main thing that sets the continuous force, so a closer set too strong or sized too large for the door is a common reason a door fails the limit.
The 5-second closing time
The 5-second closing time is the sweep time. From 90 degrees open, the door must take at least 5 seconds to reach a point 12 degrees from the latch. Many doors that have never been adjusted close through that stretch far faster than 5 seconds. On LCN closers, Allegion describes the main speed valve as the one that sets the swing from wide open down to the last 15 degrees or so, and turning it clockwise closes the door slower. Slowing it brings the time up without changing how hard the door is to open.
How the two settings work together
Those two settings work together. Increasing spring power makes a door close firmly but harder to open (Allegion: clockwise on the spring adjustment gives more closing power and makes the door harder to open). Slowing the sweep valve makes it close slowly without making it heavier. A good ADA adjustment uses both.
Typical ADA closer problems
| Problem | Cause | Fix |
|---|---|---|
| Interior door is hard to push or pull | Spring power too high, or closer too large | Lower spring power, or replace with a closer sized for the door |
| Door closes too quickly for a wheelchair user | Sweep valve too fast | Slow the sweep so the 90-degree-to-12-degrees time is 5 seconds or more |
| Door will not latch after lowering the force | Spring now too weak for the latch | Adjust latch speed, check hinges and latch, or replace the closer |
| Force changes with the weather | Wind or air pressure differences | Check closer size, door seals and building pressure |
Measuring the force
Section 404 states the limits but does not lay out a test procedure, and its advisory describes the opening force as the continuous force needed to open the door fully. A technician doing an ADA check measures with instruments, a force gauge for opening force and a stopwatch for closing time, rather than by feel. This page only explains the numbers. It is not a compliance certification, and your building owner or accessibility consultant makes the final decision on compliance.
What ADA door closer compliance in Atlanta includes, and what to have ready
The job includes
- Measuring opening force with a force gauge and closing time with a stopwatch.
- Slowing the sweep so the 90-degree-to-12-degree time is 5 seconds or more.
- Lowering spring power or replacing an oversized closer, then checking the door still latches.
- Reporting the figures so the building owner or accessibility consultant can decide on compliance.
Have ready when you call
- Whether the door is interior or exterior and whether it is fire-rated.
- The complaint: hard to push or pull, or closing too fast.
- Closer brand and size if readable.
- Who decides compliance for the building, the owner or an accessibility consultant.
ADA door closer compliance in Atlanta: Georgia rules, permits and inspection
Which doors the ADA figures cover
ADA door closer compliance in Atlanta applies the 2010 ADA Standards to doors on an accessible route, and the federal standard sits beside Georgia's fire rules and the local code. 2010 ADA Standards, section 404
Fire doors
Fire doors follow the authority having jurisdiction: under 404.2.9 a fire door has the minimum opening force allowable by the appropriate administrative authority, and NFPA 80 5.2.4.2 requires the closer to close and latch it. 2010 ADA Standards, section 404 NFPA 80, section 5.2
Georgia adoption and exterior doors
Georgia's Rule 120-3-3-.04 adopts NFPA 80, 2022 Edition. Exterior hinged doors have no pound figure in 404.2.9, so the building owner or the local code office says what applies. Call to confirm for your door. Georgia Rule 120-3-3-.04
Why call this number for ADA door closer compliance in Atlanta
Atlanta only
This site covers door closers in Atlanta, Georgia and no other city.
Numbers, not feel
Opening force and closing time are measured with a force gauge and a stopwatch.
Cited, not guessed
Every figure on this page links to the 2010 ADA Standards or a manufacturer document, and this site does not certify a door.
One call, no forms
The phone is the only way in: call the number on this page and describe the door.
Standards and primary sources behind this page
- 2010 ADA Standards, section 404U.S. Department of Justice (ada.gov)
- LCN concealed closer guideAllegion (LCN), hosted by The Builder's Supply
- Allegion: how to adjust a door closerAllegion (LCN)
- NFPA 80, section 5.2National Fire Protection Association
- Georgia Rule 120-3-3-.04Georgia Office of Commissioner of Insurance and Safety Fire (OCI)
ADA door closer compliance in Atlanta: common questions
What is the ADA limit for pushing or pulling an interior door?
ADA door closer compliance in Atlanta limits an interior hinged door to 5 pounds (22.2 N) maximum opening force under section 404.2.9 of the 2010 ADA Standards. The advisory says that is the continuous force to fully open the door, not the initial force to overcome inertia, and the limit does not apply to retracting latch bolts. Fire doors are the exception, where the minimum force allowed by the appropriate administrative authority applies.
How long does an ADA door closer take to close?
An ADA-compliant door closer in Atlanta takes at least 5 seconds to close through the sweep. Section 404.2.8.1 requires the closer to be adjusted so the door takes at least 5 seconds to move from 90 degrees open to a position 12 degrees from the latch. Spring hinges have a separate figure in 404.2.8.2: at least 1.5 seconds from 70 degrees to closed. On a closer the time is set with the main speed (sweep) valve.
Does the 5-pound limit apply to exterior doors?
ADA door closer compliance in Atlanta uses the 5 pound limit of section 404.2.9 for interior hinged doors and for sliding and folding doors. It gives no figure for exterior hinged doors. Ask the building owner or the local code office what applies to your doors.
If I reduce the spring power, will the door still latch?
Reducing spring power on a door closer in Atlanta for ADA reasons does not always leave the door able to latch. Lower spring power means less force to close, and some doors then stop short of the latch. LCN's own guide warns that a closer adjusted for reduced opening force may not reliably close and latch the door. Adjusting latch speed and checking hinges and latch alignment helps, and in some cases a different closer or a power operator is the right answer.
Can you certify that my door meets the ADA?
ADA door closer compliance in Atlanta is explained here as the standard figures only, and this page cannot certify a door. Compliance is a determination for the building owner or an accessibility professional. A technician can measure and set the closer to the figures.
More door closer repair in Atlanta
- Door closer repairSymptoms, closer types and what to have ready
- Surface-mounted closersBody and arm on the door or frame
- Concealed overhead closersCloser hidden in the door or frame head
- Floor closersFloor spring under glass and heavy doors
- Closer adjustmentSlamming, slow and non-latching doors
- Leaking closersOil on the closer, door or floor
- Fire door closersSelf-closing and latching fire doors
- Closer replacementWhen to replace, sizing and brands
Sources for ADA door closer compliance in Atlanta
- 2010 ADA Standards for Accessible Design, sections 404.2.7, 404.2.8, 404.2.9 and 309.4U.S. Department of Justice (ada.gov) · primary. Text read directly from the ada.gov page on 2026-11-13 (saved copy: sources/ada2010.txt).
- LCN Concealed Closer Series product selection guide (2010, 2030, 3030, 3130, 5010, 5030, 6030 series)Allegion (LCN), hosted by The Builder's Supply · manufacturer. Read 2026-11-13.
- Allegion knowledge base: How do you adjust a door closer? (LCN and Falcon closers)Allegion (LCN) · manufacturer. Read 2026-11-13.
- NFPA 80, Standard for Fire Doors and Other Opening Protectives, section 5.2 (inspection and testing: 5.2.1 and 5.2.4.2)National Fire Protection Association · primary publication page; full code text is behind NFPA's login. NFPA's own text could not be opened without an account. The wording below was confirmed from two published quotations: the NFPA 80 (2010) highlights sheet reproduced by Deltrex USA and Life Safety Services' article quoting sections 5.2.1 and 5.2.4.2. Item numbers inside 5.2.4.2 differ between editions, so only the section number is cited.
- Georgia Rule 120-3-3-.04, State Minimum Fire Safety Standards with Modifications (adopts NFPA 80, 2022 Edition with no modifications, and NFPA 101, 2024 Edition with modifications, including 7.2.1.8.2.1 on spring hinges and self-closing devices) (also official rule text)Georgia Office of Commissioner of Insurance and Safety Fire (OCI) · primary. Read the OCI PDF (dated Nov 5, 2025) on 2026-11-13: item (58) NFPA 80, 2022 Edition, No modifications; item (72) NFPA 101, 2024 Edition; Chapter 7 modifications add 7.2.1.4.1(8) and 7.2.1.8.2.1. Rules change, so confirm current adoption with the AHJ.