Fire Door Closer Repair in Atlanta

Fire door closer repair in Atlanta fixes labeled fire doors that do not close and latch by themselves, using NFPA 80 section 5.2.4.2 as the checklist.

Call (470) 256-0441

Direct line (470) 256-0441

  • Atlanta only
  • Call, no forms
  • Cites the 2010 ADA Standards and NFPA 80
Stairwell emergency exit door under an illuminated exit sign with a closer mounted above the door, shown for fire door closer repair in Atlanta
A stairwell exit door. A door in this position has to close and latch by itself every time.
The short answer

Fire door closer repair in Atlanta: the short answer

Fire door closer repair in Atlanta restores the one job a closer has on a labeled fire door: the door must be closed when a fire starts. NFPA 80 section 5.2.4.2 lists as a minimum check that the self-closing device is operational, meaning the active door completely closes when operated from the full open position, and that the latching hardware secures the door.

Fire door closer repair in Atlanta follows NFPA 80 section 5.2.1, which calls for fire door assemblies to be inspected and tested not less than annually, with a signed written record kept for the authority having jurisdiction. Georgia's Rule 120-3-3-.04 adopts NFPA 80, 2022 Edition, with no modifications.

A failed closer, a latch dragging on the strike, a wedge or a bad add-on are the usual reasons a rated door stays open or ajar. Fire door closer repair in Atlanta also keeps the door usable, so see ADA door closer compliance for opening force, and a leaking closer is replaced (see leaking door closer repair).

Codes and figures

Fire door closer repair in Atlanta: quick facts and sources

1per year

Fire door assemblies are inspected and tested not less than annually under NFPA 80, section 5.2.1; Georgia adopts the 2022 Edition without changes.

Georgia Rule 120-3-3-.04 (NFPA 80, 2022 Edition)
2022edition

NFPA 80, the fire door standard, is adopted in Georgia in its 2022 Edition with no modifications.

Georgia Rule 120-3-3-.04 (NFPA 80, 2022 Edition)
2024edition

NFPA 101 is adopted in its 2024 Edition with Georgia modifications, including 7.2.1.8.2.1 on self-closing devices for fire-rated doors.

Georgia Rule 120-3-3-.04 (NFPA 101, 2024 Edition)
Annual inspection
NFPA 80 section 5.2.1 calls for fire door assemblies to be inspected and tested not less than annually, and for a signed written record to be kept for the authority having jurisdiction. NFPA 80, section 5.2
Self-closing and latching
NFPA 80 section 5.2.4.2 lists as minimum items that the self-closing device is operational and that the latching hardware operates and secures the door when closed. NFPA 80, section 5.2
Hardware condition
NFPA 80 section 5.2.4.2 also lists that the door, frame, hinges and hardware are secured, aligned and in working order with no missing or broken parts, and that no auxiliary hardware interferes with operation. NFPA 80, section 5.2
Georgia adoption
Georgia Rule 120-3-3-.04 lists NFPA 80, 2022 Edition, as adopted with no modifications, so the fire door closer rules are the unmodified NFPA 80 text, and lists NFPA 101, 2024 Edition, as adopted with modifications. Georgia Rule 120-3-3-.04
Spring-operated closing devices
Georgia's modification 7.2.1.8.2.1 prohibits spring loaded hinges or spring operated self-closing devices not listed for use with rated fire door assemblies as closing devices for fire rated doors. Georgia Rule 120-3-3-.04
ADA opening force
Under 404.2.9 a fire door has the minimum opening force allowable by the appropriate administrative authority, and the ADA gives no pound figure for it. 2010 ADA Standards, section 404
How a call works

How a fire door closer repair call in Atlanta works

Step 1

Call and describe the door and its label

Say where the door is, what the label on the edge or frame says, and what the door does.

Step 2

Check the closer against NFPA 80 5.2.4.2

The door must close completely from full open, latch, and carry no broken, missing or interfering hardware.

Step 3

Repair or replace to suit the rated opening, then test

Latch speed and spring power are adjusted, a failed closer is replaced with one that suits the opening, and the door is tested closed and latched.

Cost factors

How much does fire door closer repair cost in Atlanta?

How much fire door closer repair costs in Atlanta depends on the rated opening and what is wrong with the closer, so this page gives no figures. The factors are:

  • Closer type and size. It has to suit the rated opening and the door.
  • Adjust, repair or replace. Latch speed and spring power are adjusted; a failed closer is replaced.
  • Latch and strike condition. A latch dragging on the strike keeps a door ajar.
  • Wedges and add-ons. Interfering hardware is removed or corrected.
  • Number of rated doors. Each door on the list is checked on its own.
  • Door and frame condition. Hinges, frame and mounting area.

For a figure on your door, call for a quote at (470) 256-0441.

One call

Fire door not closing or latching? Call now.

Give the label and what the door does, and fire door closer repair in Atlanta starts there.

Call (470) 256-0441

Why the closer matters on a fire door

A fire door only does its job if it is closed when a fire starts. That is the closer's role. On a labeled fire door in a stairwell, corridor or rated wall, NFPA 80 section 5.2.4.2 lists as a minimum check that the self-closing device is operational, meaning the active door completely closes when operated from the full open position, and that the latching hardware operates and secures the door in the closed position.

Photo note: the picture shows a stairwell exit door with a closer fixed above it, the kind of door where a failed closer is a life-safety issue.

Fire door closer checks under NFPA 80Four steps: open the fire door fully, release it, check that it closes completely, and check that the latch engages. NFPA 80 5.2.4.2 lists the self-closing device and the latching hardware among the items checked, and 5.2.1 requires inspection and testing at least annually with a signed record; Georgia adopts NFPA 80, 2022 Edition.Closer and latch items in an NFPA 80 inspection (5.2.4.2, 5.2.1)Open the doorto the full open positionRelease itthe closer takes overCloses completelyself-closing device worksLatch engagesdoor secured when closedInspected and tested not less than annually, with a signed written record (NFPA 80 5.2.1)Georgia Rule 120-3-3-.04 adopts NFPA 80, 2022 Edition, with no modificationsA closer that fails either test is adjusted or replaced with a closer that suits the rated opening.
The closer and latch items from NFPA 80 section 5.2.4.2, plus the annual test in 5.2.1.

Closer checks on a fire door

NFPA 80 section 5.2.1 requires fire door assemblies to be inspected and tested not less than annually, with a signed written record kept for the authority having jurisdiction. Section 5.2.4.2 lists the minimum items to verify. The table sets the closer-related items beside what a pass looks like.

Closer checks on a fire door and what a pass looks like
CheckWhat a pass looks likeCommon failureBasis
Self-closing from fully openThe active door completely closes when operated from the full open positionCloser failed, disconnected or leakingNFPA 80 5.2.4.2
LatchingLatching hardware operates and secures the door in the closed positionLatch speed too slow, bolt dragging on the strikeNFPA 80 5.2.4.2
Closer attachmentHardware secured, aligned and in working order; no parts missing or brokenLoose screws, bent arm, missing partsNFPA 80 5.2.4.2
Items that interfereNo auxiliary hardware that interferes with or prohibits operationDoor wedged open, a bad add-on fittedNFPA 80 5.2.4.2
Closer leaksNo oil on closer or doorSeal failure, loss of closing controlTechnician check, not an NFPA 80 item

Fire door closer problems and repairs

Fire door closer problems and typical repairs
ProblemTypical repair
Door does not latch after closingAdjust latch speed and spring power, then check the latch
Door stays openReconnect or replace the closer arm or closer, remove wedges
Closer leaking oilReplace with a closer suitable for the opening
Door slams hardSlow the sweep and latch speed
Closer missingInstall a closer suitable for the rated opening
Check the label. A fire-rated door has a label on the door edge or frame. If a replacement closer is needed, it has to suit the rated opening. Questions about what is allowed go to the authority having jurisdiction.
Georgia rules. Georgia's Rule 120-3-3-.04 adopts NFPA 80, 2022 Edition, with no modifications. For fire doors in the means of egress it adds 7.2.1.8.2.1 to NFPA 101 (2024 Edition): spring loaded hinges or spring operated self-closing devices not listed for use with rated fire door assemblies are prohibited as closing devices for fire rated doors. Rules change, so confirm current adoption with the authority having jurisdiction.
Scope of the job

What fire door closer repair in Atlanta includes, and what to have ready

The job includes

  • Checking that the door closes completely from full open and that the latch secures it.
  • Replacing or reconnecting the closer, arm or shoe, and removing wedges or interfering add-ons.
  • Adjusting latch speed and spring power, then checking the latch and strike.
  • Replacing a leaking or missing closer with one that suits the rated opening.

Have ready when you call

  • The label on the door edge or frame, or a phone photo of it.
  • Where the door is: stairwell, corridor or rated wall.
  • What it does: stays open, closes but does not latch, or slams.
  • The date of the last annual fire door inspection, if one is on file.
Georgia rules

Fire door closer repair in Atlanta: Georgia rules, permits and inspection

Fire door closer repair in Atlanta is governed by NFPA 80 as adopted in Georgia: Rule 120-3-3-.04 adopts NFPA 80, 2022 Edition, with no modifications, and adds 7.2.1.8.2.1 to NFPA 101 (2024 Edition) on spring-operated closing devices. Georgia Rule 120-3-3-.04

NFPA 80 section 5.2.1 sets annual inspection and testing with a signed written record, and section 5.2.4.2 lists the minimum items verified. NFPA 80, section 5.2

Questions about what closer is allowed on a rated opening go to the authority having jurisdiction, and rules change, so confirm current adoption. Call to confirm for your door.

Why this number

Why call this number for fire door closer repair in Atlanta

Atlanta only

This site covers door closers in Atlanta, Georgia and no other city.

Closers on rated doors

The work is the closer and the latching of a fire door, not other fire door parts.

Cited, not guessed

Every rule on this page links to NFPA 80, Georgia's rule or the ADA Standards.

One call, no forms

The phone is the only way in: call the number on this page and describe the door.

Standards cited

Standards and primary sources behind this page

Questions

Fire door closer repair in Atlanta: common questions

How do I know if a door is fire-rated?

A fire-rated door in Atlanta is identified by a label, which is the first thing fire door closer repair looks for. Look for a metal or printed label on the door edge, usually near the hinge side, and on the frame. The label lists the rating. If you cannot find one, ask the building owner or manager.

Can I prop a fire door open?

Fire door closer repair in Atlanta does not include propping the door open with a wedge or a block. NFPA 80 5.2.4.2 includes verifying that nothing interferes with the door's operation. Some doors are held open by a device made for the purpose that releases the door when a fire alarm sounds. Ask the building owner or fire marshal what is allowed.

My fire door closes but does not latch. Is that a closer problem?

A fire door in Atlanta that closes but does not latch can be a closer problem. A closer too slow at the latch or a spring too weak for the latch can leave the door ajar. A latch that drags on the strike is the other usual cause.

Does a fire door closer have to be replaced with the same brand?

Fire door closer repair in Atlanta does not require the same brand, but the closer has to suit the rated opening. A technician matches the size and mounting to the door and checks with you on any rating questions.

How often should fire door closers be checked?

Fire door closers in Atlanta fall under the NFPA 80 annual inspection. NFPA 80 section 5.2.1 calls for fire door assemblies to be inspected and tested not less than annually, with a signed written record. Many building owners fold the closer check into that yearly inspection.